Submersible Pump Cable TYPE THW-FLAT with Ground 75°C/600V |
|
Description & Features:
UL listed Type THW general purpose flat submersible pump
cable.
Copper stranding covered with a tough PVC
insulation applied directly over the conductors. A thin
integral web between conductors assures easy separation to facilitate
installation yet provide flexibility and mechanical protection.
- UL Listed as TYPE THW Submersible Pump Cable
- Oil and grease resistant
- Abrasion Resistant
- Sequential footage marks
Applications:
- For use within the well casing to supply power to the submersible pump.
- Designed for use where flexibility during installation and operation are required
|
Construction:
Conductors: Stranded soft annealed copper
Insulation/Assembly: Copper conductors, including the ground conductor,
are configured flat and parallel. Thermo-plastic polyvinyl chloride (PVC) is applied directly over
the conductors with a thin integral web between adjacent conductors. Conductors are phase identified.
Temperature: 75C
Voltage: 600 Volts
Specifications and Standards:
UL Standard 83
RoHS Compliant
|
TWO OR THREE WIRE CONDUCTOR WITH GROUND
Standard Packaging 500'
Call for longer requirements 866-960-9621
| Part Number |
Conductor |
Dimensions (Inches) |
Shipping Weight 500'/(Lbs) |
Ampacity NEC§ |
Shopping Cart
View Cart
|
| |
Size |
Ground Wire |
Insulation |
O.D. |
|
|
|
PMPY14/2GG*
(Cut Lengths) |
14/2 (7 str) |
14 (7 str) |
.045 |
.166 x .588 |
39 |
N/A |
|
| PMPY14/2GG |
14/2 (7 str) |
14 (7 str) |
.045 |
.166 x .588 |
39 |
N/A |
|
| PMPY12/2GG |
12/2 (7 str) |
12 (7 str) |
.045 |
.190 x .570 |
63 |
20 |
|
| PMPY10/2GG |
10/2 (7 str) |
10 (7 str) |
.045 |
.211 x .663 |
84 |
30 |
|
| PMPY8/2GG |
8/2 (7 str) |
10 (7 str) |
.045 |
.238 x .749 |
120 |
50 |
|
| PMPY12/3GG |
12/3 (7 str) |
12 (7 str) |
.045 |
.190 x .752 |
78 |
20 |
|
| PMPY10/3GG |
10/3 (7 str) |
10 (7 str) |
.045 |
.211 x .836 |
106 |
30 |
|
| PMPY8/3GG |
8/3 (7 str) |
10 (7 str) |
.060 |
.268 x 1.056 |
149 |
50 |
|
| PMPY6/3GG* |
6/3 (19 str) |
8 (19 str) |
.060 |
.306 x 1.230 |
225 |
65 |
|
| PMPY4/3GG* |
4/3 (19 str) |
8 (19 str) |
.060 |
.352 x 1.322 |
561 |
85 |
|
* Cut Lengths Available
Starting at 200 feet - Add $25 Cut and Spool Charge
§ Per Table 310-16 of the NEC
All values are nominal; all weights are exclusive of
packaging. All diameters and weights are subject to normal
manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale.
Need a Submersible Splice Connection Kit ?
Splice Kit Instructions
|
Submersible Pump Cable TYPE THW-Heavy
Duty FLAT BLACK JACKETED with Ground 75°C/600V |
|
Description & Features:
UL listed Type THW heavy duty flat submersible pump
cable is
a multi-purpose cable with parallel, individually
insulated, color
coded conductors and an overall jacket. Construction
provides flexible
copper stranding insulated with Type THW (PVC)
compound.
A tough PVC jacket, with a non-penetrating web, is
easily stripped
to facilitate installation yet provide optimum
flexibility, mechanical
protection and crush resistance.
- UL Listed as TYPE THW Submersible Pump Cable
- Acid, alkali, oil and grease resistant
- Weather, ozone and sunlight resistant jacket
- Abrasion and crush resistant
- Sequential footage marks
Applications:
- For use within the well casing to supply power to the submersible pump.
- Designed for use where flexibility during installation and operation are required
|
Construction:
Conductors: Stranded soft annealed copper
Color coding: black, red, yellow, green (ground)
Assembly: The insulated conductors, including the grounding conductor, are configured flat and parallel without fillers
Jacketing: Black thermoplastic polyvinyl chloride (PVC) applied directly over the conductors with a non-penetrating web
Temperature: 75C
Voltage: 600 Volts
Specifications and Standards:
UL Standard 83
RoHS Compliant
|
TWO AND THREE CONDUCTORS WITH GREEN INSULATED
GROUNDING CONDUCTOR
Standard Packaging 500'
Call for longer requirements 866-960-9621
| Part Number |
Conductor Size, AWG |
Dimensions (Inches) |
Shipping Weight 500'/(Lbs) |
Ampacity NEC§ |
Shopping Cart
View Cart
|
| |
Power |
Ground |
Insulation |
Jacket |
O.D. |
|
|
|
| PMP12/3GGHD |
12/3 (19 str) |
12 (19 str) |
.045 |
.045 |
.280 x .840 |
110 |
20 |
|
| PMP12/2GGHD |
12/2 (19 str) |
12 (19 str) |
.045 |
.045 |
.280 x .654 |
91 |
20 |
|
| PMP10/3GGHD |
10/3 (19 str) |
10 (19 str) |
.045 |
.045 |
.305 x .940 |
143 |
30 |
|
| PMP10/2GGHD |
10/2 (19 str) |
10 (19 str) |
.045 |
.045 |
.305 x .729 |
120 |
30 |
|
| PMP8/3GGHD* |
8/3 (19 str) |
10 (19 str) |
.060 |
.045 |
.364 x 1.120 |
202 |
50 |
|
| PMP8/2GGHD |
8/2 (19 str) |
10 (19 str) |
.060 |
.045 |
.380 x .830 |
153 |
50 |
|
| PMP6/3GGHD* |
6/3 (19 str) |
8 (19 str) |
.060 |
.045 |
.414 x 1.336 |
286 |
65 |
|
| PMP4/3GGHD* |
4/3 (19 str) |
8 (19 str) |
.060 |
.045 |
.465 x 1.489 |
382 |
85 |
|
| PMP2/3GGHD* |
2/3 (19 str) |
6 (19 str) |
.060 |
.045 |
.535 x 1.749 |
558 |
115 |
|
| PMP1/03GGHD* |
1/03 (19 str) |
6 (7 str) |
.080 |
.060 |
.660 x 1.990 |
856 |
150 |
|
| PMP2/03GGHD* |
2/03 (19 str) |
6 (7 str) |
.080 |
.060 |
.700 x 2.120 |
1015 |
175 |
|
| PMP3/03GGHD* |
3/03 (19 str) |
4 (7 str) |
.080 |
.060 |
.734 x 2.314 |
1249 |
200 |
|
| PMP4/03GGHD* |
4/03 (19 str) |
4 (7 str) |
.080 |
.060 |
.800 x 2.490 |
1486 |
230 |
|
| PMP250/3GGHD* |
250/3 (37 str) |
4 (7 str) |
.095 |
.080 |
.925 x 2.807 |
1834 |
235 |
|
| PMP350/3GGHD* |
350/3 (37 str) |
3 (7 str) |
.095 |
.080 |
1.031 x 3.153 |
2419 |
310 |
|
* Cut Lengths Available (minimum length X 100' + $25 cut charge)
§ Per Table 310-16 of the NEC All values are
nominal; all weights are exclusive of packaging. All diameters and
weights are subject to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale.
Single Phase Sizing Table:
Table 11A
| Motor Rating |
75° C Insulation - AWG
Copper Wire Size |
| Volts |
HP |
KW |
14 |
12 |
10 |
8 |
6 |
4 |
3 |
2 |
1 |
0 |
00 |
000 |
0000 |
|
115 |
1/2 |
.37 |
100 |
160 |
250 |
390 |
620 |
960 |
1190 |
1460 |
1780 |
2160 |
2630 |
3140 |
3770 |
|
230 |
1/2 |
.37 |
400 |
650 |
1020 |
1610 |
2510 |
3880 |
4810 |
5880 |
7170 |
8720 |
|
|
|
|
3/4 |
.55 |
300 |
480 |
760 |
1200 |
1870 |
2890 |
3580 |
4370 |
5330 |
6470 |
7870 |
9380 |
|
|
1 |
.75 |
250 |
400 |
630 |
990 |
1540 |
2380 |
2960 |
3610 |
4410 |
5360 |
6520 |
7780 |
9350 |
|
1 1/2 |
1.1 |
190 |
310 |
480 |
770 |
1200 |
1870 |
2320 |
2850 |
3500 |
4280 |
5240 |
6300 |
7620 |
|
2 |
1.5 |
150 |
250 |
390 |
620 |
970 |
1530 |
1910 |
2360 |
2930 |
3620 |
4480 |
5470 |
6700 |
|
3 |
2.2 |
120 |
190 |
300 |
470 |
750 |
1190 |
1490 |
1850 |
2320 |
2890 |
3610 |
4470 |
5550 |
|
5 |
3.7 |
0 |
110 |
180 |
280 |
450 |
710 |
890 |
1110 |
1390 |
1740 |
2170 |
2680 |
3330 |
|
7 1/2 |
5.5 |
0 |
0 |
120 |
200 |
310 |
490 |
610 |
750 |
930 |
1140 |
1410 |
1720 |
2100 |
|
10 |
7.5 |
0 |
0 |
0 |
160 |
250 |
390 |
490 |
600 |
750 |
930 |
1160 |
1430 |
1760 |
|
15 |
11 |
0 |
0 |
0 |
0 |
170 |
270 |
340 |
430 |
530 |
660 |
820 |
1020 |
1260 |
Lengths not in bold type meet the U.S. National Electric Code Ampacity for either individual conductors or jacketed 75°C cable.
Lengths in bold type meet the National Electric Code Ampacity
only for individual conductor 75°C cable, in free air or water,
not in magnetic enclosure or conduit. If any other cable is
used, the National Electric Code as well as the local codes
should be observed. Flat molded and web cable is considered
jacketed cable. Cable lengths in Table 11A allows for a 5%
voltage drop running at maximum nameplate amperes. If 3% voltage
drop is desired multiply Table 11A lengths by .6 to get maximum
cable length. Table 11A is based on copper wire. If aluminum
wire is used, it must be two sizes larger than copper wire and
oxidation inhibitors must be used on connections. EXAMPLE: If
Table 11A calls for #12 copper wire, #10 aluminum wire would be
required. The portion of the total cable length which is between
the supply and single-phase control box with a line contactor,
should not exceed 25% of total maximum allowable to ensure
reliable contactor operation. Single-phase control boxes without
line contactors may be connected at any point in the total cable
length.